The G9000 comes with an industry-leading three-year onsite warranty. It is designed for stand-alone or parallel use in up to four-unit configurations without requiring the use of a special switchgear cabinet.
The Toshiba G9000 Uninterruptible Power System (UPS) utilizes state-of-the-art design and construction to deliver industryleading efficiency, reliability, and flexibility to meet today’s critical power demands.
Using the new Toshiba IGBT technology in the rectifier/converter, DC/DC chopper, and the inverter sections of the UPS, the G9000's double-conversion topology provides an AC/DC/AC efficiency of 96.5% at loads from 50% to 100%. Even at 20% loading, the efficiency remains greater than 94%. This is 10% to 20% better than current industry systems, making the G9000 excellent for N+1 parallel systems where loads are typically 30-40%.
Fast-switching IGBT control technology delivers up to 97%
efficiency.
The G9000’s transformerless design makes it far lighter than conventional UPSs, and gives it a much smaller footprint compared to similar sized UPSs. With its compact size, the G9000 has the highest energy density per square foot of any UPS of similar capacity.
Model Number |
T90S3S08KS6XSN |
T90S3S10KS6XSN |
T90S3S16KS6XSN |
T90S3S22KS6XSN |
|
| Capacity | KVA/KW |
80/72 |
100/90 |
160/144 |
225/202.5 |
| Topology | True On-Line, Double Conversion, Advanced Multi-Level IGBT Technology |
||||
| Input | Voltage | 480 V, Three-Phase, Three-Wire + Ground/Bypass Input, 480 V, Three-Phase, Three-Wire + Ground |
|||
| Voltage Range | 480 V, -20% to +15% (384 to 552 V Without Utilizing Battery) |
||||
| Power Factor | Greater than 0.99 |
||||
| Current THD | <3% at 100% Load (No Input Filter Required) |
||||
| Frequency | 60 Hz (± 10%) |
||||
| Output | Voltage | 480 V, Three-Phase, Three-Wire + Ground |
|||
| Frequency | 60 Hz, ±0.01% (In Free-Running Mode) |
||||
| Voltage Regulation | ±1.0% (0.5% Typical) |
||||
| Power Factor | 0.9 Lagging |
1.0 (Unity) |
|||
| Power Factor Range | 0.9 Lagging to 0.95 Leading |
||||
| Voltage THD | <2% for Linear Load, <5% for Non-Linear Load |
||||
| Overload (Inverter) | 125% for 2 Minutes; 150% for 60 Seconds |
||||
| Overload (Bypass) | 1000% for One Cycle |
500% for One Cycle |
|||
| Battery | DC Link | 480 VDC |
|||
| Environment | Temperature Range | 32° to 104°F (0° to 40°C) |
|||
| Relative Humidity | 5% to 95% Non-Condensing |
||||
| Heat Rejection | 10,771 BTUs/Hour |
13,463 BTUs/Hour |
17,821 BTUs/Hour |
25,060 BTUs/Hour |
|
| Efficiency (Full-Load) | 95.80% |
95.80% |
96.50% |
96.50% |
|
| Efficiency (20% Load) | 92.50% |
92.50% |
94.70% |
94.90% |
|
| Altitude | 7380 Feet Maximum Without Derating (2250 Meters) |
||||
| Audible Noise | 70 dBA at 1 Meter |
||||
| Dimensions | Dimensions (W x D x H) | 27.6 x 32.8 x 80.6 in.(700 x 832 x 2047 mm) |
35.4 x 32.8 x 80.6 in.(900 x 832 x 2047 mm) |
||
| Weight | 855 lbs. (388 kg) |
855 lbs. (388 kg) |
1160 lbs. (526 kg) |
1230 lbs. (558 kg) |
|
| Features | Digital Signal Processor (DSP) Control, Fully Digital IGBT Converter & Inverter, High Efficiency Over Wide Load Range, Transformer-Less Design, N+1 and N+N (Up to Four in Parallel) Capability, Dual-Input Feed, Electronic Battery Isolation, RS232 and Dry Contact Interface, Small Footprint, Lightweight Design |
||||
| Standards | UL 1778, CUL, ISO9001, ISO14001, ANSI C62.41 (IEEE 587), FCC Class A, Article 47, Part 15.B |
||||
| Warranty | Three Years Onsite (Optional Two Year Extended Warranty) |
||||
Toshiba has recently completed construction of a 1500 KW Witness Test Facility at its plant in Houston, Texas. Customers can now perform witness testing to validate their system’s performance specifications in all operating modes prior to taking delivery. Multi-module parallel configurations, including battery or flywheel backup, can be assembled and tested in all modes before shipment for final installation.
* Conditional to system startup by an Authorized Toshiba UPS Service Provider. See three-phase warranty for details.